Copernico TL

Applications

  • LV photovoltaic power plants
  • MV/HV photovoltaic power plants
  • Stand alone photovoltaic power plants with energy storage system
  • Grid connected photovoltaic power plants with energy storage system
  • Hybrid power generation station
  • Peak shaving
  • Load balancing
  • Time shifting
  • High reliability

    • Longer time between maintenance activities
    • Reduction of energy production losses due to inverter failure
  • High efficiency

    • Some competitors declare only the maximum efficiency
    • Copernico’s efficiency is measured in the real operating conditions with all the auxiliary circuit connected
  • Low current distortion

    • Competitor’s average values are in the range 3–4%
    • Lower current distortion leads to a general reduction of the energy losses in conductors and transformers
  • Wide MPPT range

    • One of the widest (370Vdc) among inverter manufacturers
    • The energy production of the PV array is maximised
  • High output voltage in TL series (300 Vac)

    • Competitor’s average values 270–280 Vac y
    • Higher voltage = Lower current
    • Smaller AC cables and circuit breakers
  • Simplified installation

    • Single mechanical structure up to 500 kW
    • Space saving thanks to:
    • Small foot-print for all the range
    • Reduced installation clearances
  • Wide range availability of accessories for PV plants

    • Array Monitor (stings boxes)
    • Green Power Guardian (monitoring System)
    • PV sensors to measure environmental temperature, PV panel temperature, solar radiation

Технические характеристики

Copernico TL

Rating (kVA) 20 30 50 100 150 200 250 350 500
Nominal power (kW) 20 30 50 100 150 200 250 350 500
Max PV power (kWp) 24 35 60 120 180 240 295 410 580
Dimensions WxHxD (mm) 690x1345x895 800x1900x800 1000x2100x800 1600x2100x1000
Weight (kg) 260 271 320 415 500 635 686 1150 1372

Input

Maximum voltage 1000 V
MPPT range voltage 450 ÷ 820 V
Maximum current (A) 46 69 115 230 345 460 570 795 1140
Input protection Isolator PV switch + fuses Isolator PV switch

Output

Nominal voltage 300 V 3-phase with integrated transformer
Frequency 50/60 Hz
Power factor 0.99 Cos Ø depending on grid regulation
Current harmonics (THD) < 2 % @ nominal power and sinusoidal voltage
Output protection Electronic short-circuit protection - fuses - contactor
Maximum efficiency (%) >96.76 >97.21 >96.97 >97.37 >97.67 >97.73 >97.79 >97.95 >98.08
European maximum efficiency (%) >94.77 >95.86 >96.01 >96.60 >97.03 >97.18 >97.17 >97.45 >97.69
Loss under normal operation (Wh) 650 850 1500 2600 3500 4500 5500 8200 12000
Nominal power (BTU) 2200 2900 5100 8800 12000 15300 18700 27900 40900
Max PV power recommended (kWp) 24 35 60 120 180 240 295 410 580

Connectivity and function extensions

Front panel LCD display, mimic LED panel and keyboard
Remote communication Modbus RS485

System

Protection degree IP 20
Colour RAL 7035
Accessibility Front access

Environmental

Operating temperature -10 °C ÷ +50 °C
Storage temperature -10 °C ÷ +70 °C
Non-condensing relative humidity <95%
Altitude < 1000 m above sea level
Audible noise at 1 meter (dBA) <68

Standards and certifications

Quality assurance, environment, health and safety ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007
Safety IEC 62103 - EN 50178
EMC IEC EN 61000-6-2, IEC EN 61000-6-4
Protection degree IEC EN 60529
Marking CE