Tech Specs
STS 300: Centralized Static Transfer Switches 3-phase STS 100-3000 A
Rating (A)* |
100 |
250 |
400 |
630 |
800 |
1000 |
1250 |
Dimensions WxDxH (mm)** |
820x835x1475 |
1220x860x1900 |
2000x1000x2100 |
Weight (kg)** |
265 |
290 |
305 |
615 |
660 |
1000 |
1450 |
*rating up to 3000 A on request **3-pole version
Input
Connection type |
Hardwired 4w |
Nominal voltage |
208/380/400/415/440/480 Vac 3-phase with neutral |
Voltage tolerance |
±10% (up to ±20% on request) |
Frequency and range |
50/60 Hz, ±2 Hz (up to ±4 Hz on request) |
Source harmonic voltage content |
Unlimited (if THD>20% transfer time ≤10ms) |
Transfer phase angle |
5° to 30° |
Output
Connection type |
Hardwired 4w |
Nominal voltage |
208/380/400/415/440/480 Vac 3-phase with neutral |
Frequency |
50/60 Hz |
Transfer time |
≤4 ms |
Transfer mode |
Break before make, transfer inhibit on fault |
Load power factor |
1 to 0.3 |
Maximum crest factor |
3:1 |
THD current fedback from load |
Unlimited |
Overload capacity |
125% for 30 min, 150% for 10 min, 200% for 30 s, 2000% for 1 cycle, 4000% for ½ cycle |
Efficiency (AC/AC) |
>99% |
Connectivity and function extensions
Front panel |
Graphical LCD display, mimic LED panel and keyboard |
Remote communication |
Included: dry contact relay card, RS232 and RS485 serial ports, ModBus-RTU protocol. Optional: additional dry contact relay card |
Optional function extensions |
4-pole configuration, plug-in circuit breakers, operation without neutral, panel builder execution, output distribution panels, isolation transformer |
System
Protection degree |
IP 20 (other options) |
Colour |
RAL 9005 (other options) |
Installation layout |
Wall, back to back and side by side installation allowed |
Accessibility |
Front access, bottom and top cable entry |
Environmental
Operating temperature range |
0°C to +40°C |
Storage temperature range |
-10°C to +70°C |
Altitude (AMSL) |
< 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
Audible noise at 1 m (dBA) |
<62 |
Standards and certifications
Quality assurance, environment, health and safety |
ISO 9001, ISO 14001, ISO 45001 |
Safety |
IEC/EN 62310-1 |
EMC |
IEC/EN 62310-2 |
Breakers |
IEC/EN 60947-3 |
Transfer voltage limits |
IEEE Standard 446 |
Protection degree |
IEC 60529 |
Performance |
IEC/EN 62310-3 |
Marking |
CE |