STS 300: Centralized Static Transfer Switches 3-phase STS 100-2000 A
Rating (A)* |
100** |
250** |
400 |
630 |
800 |
1000*** |
1250 |
1600 |
1800 |
2000 |
Dimensions WxDxH (mm) |
820x835x1475 |
811x980x2100 |
1211x980x2100 |
2011x980x2100 |
2311x980x2100 |
2511x980x2100 |
Weight (kg)** |
265 |
290 |
305 |
615 |
660 |
700 |
820 |
1150 |
1280 |
1400 |
*rating up to 3000 A on request **some features may not be available ***available with top or bottom cable entry, dimensions 1211x980x2100 mm (WxDxH)
Input
Connection type |
Hardwired 3w or 4w |
Nominal voltage |
380/400/415 Vac 3-phase**** |
Voltage tolerance |
From ±1% to ±20%, adjustable (default ±10%) |
Frequency and range |
50/60 Hz, from ±1% to ±10%, adjustable (default ±5%) |
Source harmonic voltage content |
Unlimited |
Transfer phase angle |
5° to 30° |
Output
Connection type |
Hardwired 3w or 4w |
Nominal voltage |
380/400/415 Vac 3-phase**** |
Frequency |
50/60 Hz |
Transfer time |
≤4 ms |
Transfer mode |
Break before make |
Load power factor |
1 to 0.3 |
Maximum crest factor |
3:1 |
THD current fedback from load |
Unlimited |
Overload capacity |
125% for 10 min, 150% for 1 min, 200% for 30 s, 1000% for 10 cycles, 2000% for 1 cycle |
Efficiency (AC/AC) |
>99% |
**** other on request
Connectivity and function extensions
Front panel |
Graphical LCD display, mimic LED panel and keyboard |
Remote communication |
Included: dry contact relay card, RS232 and RS485 serial ports, ModBus-RTU protocol. Optional: additional dry contact relay card, SNMP, ModBus over TCP/IP card; dual ModBus card |
Optional function extensions |
Thyristor protection fuses, isolation transformer, output distribution panels; other options on request |
System
Protection degree |
IP 20 (other options) |
Colour |
RAL 9005 (other options) |
Installation layout |
Wall, back to back and side by side installation allowed |
Accessibility** |
Top or bottom cable |
Top cable or busbar |
Top busbar |
**other on request
Environmental
Operating temperature range |
0°C to +40°C |
Storage temperature range |
-10°C to +60°C |
Altitude (AMSL) |
< 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
Audible noise at 1 m (dBA) |
<65 |
Standards and certifications
Quality assurance, environment, health and safety |
ISO 9001, ISO 14001, ISO 45001 |
Safety |
IEC/EN 62310-1 |
EMC |
IEC/EN 62310-2 |
Breakers |
IEC/EN 60947-3 |
Transfer voltage limits |
IEEE Standard 446 |
Protection degree |
IEC 60529 |
Performance |
IEC/EN 62310-3 |
Marking |
CE |