Galileo Plus RT is an on‑line double conversion single phase UPS that can be used in both tower and rack configurations thanks to its reversible design. Galileo Plus RT UPS is ideal for small and medium businesses, networks and servers, delivering a rated power of 1000, 2000 and 3000 VA.
Rating (VA) | 1000* | 2000* | 3000* |
Nominal power (W) | 900 | 1800 | 2700 |
UPS dimensions WxDxH (mm) | (2U)88x405x440 | (2U)88x600x440 | (2U)88x600x440 |
Battery cabinet dimensions WxDxH (mm) | (4U)176x405x440 | (2U)88x600x440 | (2U)88x600x440 |
UPS weight (kg) | 12 | 29.5 | 30 |
Connection type | IEC 320-C14 | IEC 320-C20 |
Nominal voltage | 230 Vac 1-phase | |
Voltage range | 180 to 300 Vac at full load | |
Frequency and range | 50/60 Hz, 45 to 65 Hz | |
Power factor | 0.99 | |
Current distortion (THDi) | <3% |
Connection type | 6 IEC C13 | 6 IEC C13 + 1 IEC C19 | |
Nominal voltage | 230 Vac +/-1% 1-phase | ||
Frequency | 50/60 Hz | ||
Power factor | 0.9 | ||
Overload capability | 105% continuous, 120% for 30 seconds, 150% for 10 seconds |
||
Mode of operation | On-line, Eco-mode | ||
Classification by IEC/EN 62040-3 | VFI-SS-11 |
Autonomy time internal battery (min) |
50% load | 15 | 16 | 12 |
100% load | 5 | 5 | 4 |
*Rack/Tower
Front panel | Display LCD, status LED, function keys |
Communication | Included: USB, EPO, RS232. Optional: dry contact card, SNMP card. Compatible platforms: Windows, Linux |
Operating temperature range | 0°C to +40°C |
Altitude (AMSL) | <1000 m without power reduction, > 1000 m with reduction of 1% per 100 m |
Audible noise at 1 m (dBA) | <50 |
Quality assurance, environment, health and safety |
ISO 9001:2015, ISO 14001:2015, BS OHSAS 18001:2007 |
Safety | IEC/EN 62040-1 |
EMC | IEC/EN 62040-2 |
Test and performance | IEC/EN 62040-3 | Marking | CE |