E2001 Compact

Industrial 1-Phase AC UPS 5-30 kVA

The Borri Industrial 1 -Phase UPS E2001 Compact is designed and manufactured to withstand harsh environment and operating conditions of industrial applications with state-of-the-art technology, providing reliable and customizable AC power backup in a compact standardised solution.

Borri’s E2001 Compact is a heavy-duty on-line double conversion AC Industrial UPS with full galvanic isolation. The UPS design ensures very high reliability and safe operations; its internal constructions allows for front and easy maintenance.

The design flexibility and the wide range of configurable options allows it to meet almost any customer specification.

E2001 Compact  Industrial 1-Phase UPS is a cost-effective solution delivering reliability, availability and maintainability in almost any environmental conditions.

  • Rugged rectifier thyristor bridge with input isolation transformer.
  • Large LCD panel with mimic diagram and history.
  • Wide selection of alarms, indications and measurements.
  • Built-in isolation transformer.
  • PWM IGBT Inverter Bridge.
  • Built-in manual bypass.
  • Advanced battery management.
  • Flexible in-built features.
  • Widely configurable.
  • Easy maintenance and serviceability.
  • Rugged 6-pulse thyristor bridge with isolation transformer.
  • 4 level battery charging including optional manual charge.
  • Active parallel configuration via CAN bus connection.
  • Standard configuration for cost-effective, short lead time solutions.
  • Electronic current limit.
  • 20 programmable alarm and status LEDs.
  • Built-in inverter transformer.
  • Communication ports and potential free contacts.
  • Bottom cable entry.

Tech Specs

E2001 Compact: Industrial 1-phase AC UPS 5-30 kVA

Rating (kVA) @ P.F. 0.8 vs DC Rated Voltage

110 Vdc 5 10 15 20 30
220 Vdc 5 10 15 20 30
Nominal power kW 4 8 12 16 24

Input

Input voltage 380/400/415 Vac 3-phase ±10% (others on request), 50/60 Hz ±10%
Power Factor > 0,75 (depending on rectifier technology)
Bypass input voltage 110/115/120 or 220/230/240 Vac 1-phase ±20%
(adjustable according to inverter output voltage)

Battery

DC voltage 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range)
Input voltage Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable
Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable
Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable
Battery technologies Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible

Output

Nominal voltage 110/115/120 or 220/230/240 Vac 1-phase
Frequency 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains
Voltage regulation ±1% static; ±5% dynamic (80% load change), <40 ms recovery time
Overload capacity 125% for 10 min; 150% for 1 min; 200% for 100 ms
Harmonic Distortion THDv <2% linear load; <5% non-linear load

System

Dimensions WxD (mm) 600x640x1900 800x800x2100
Cooling Forced ventilation (optional redundant fans)
Colour RAL 7035 (optional other colours)
Protection degree IP 20 as per IEC 60529 (optional up to IP 42)

Environmental

Operating temperature -10° C to 40° C (up to 55° C with de-rating) / Storage: -20° C to 70° C
Altitude < 1000 m (up to 2000 m de-rating according to EN 62040-3)
Audible noise at 1 meter (dBA) <65

User Interface

Front panel Graphic display, mimic LED panel, function keys, local EPO
Connectivity Included: USB, alarm relay card, terminal block for auxiliary contacts

Standards

Quality assurance, environment, health and safety ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007
Safety IEC EN 62040-1
EMC IEC EN 62040-2
Environmental aspects IEC EN 62040-4
Test and performance IEC EN 62040-3 VFI-SS-111
Marking CE (CSA/UL certified as optional)