Borri AC Industrial 1-Ph Uninterruptible Power System E2001 is designed and manufactured to withstand harsh environment and operating conditions of industrial applications with state-of-the-art technology, providing reliable and customizable AC power backup solutions.
Borri’s E2001 is a heavy-duty on-line double conversion AC Industrial UPS with full galvanic isolation. The UPS design ensures very high reliability, safe operations and a very low mean time to repair (MTTR), achieving the highest possible availability. The design flexibility allows it to meet almost any customer specification.
E2001 UPS is a cost-effective solution delivering reliability, availability and maintainability in almost
any environmental conditions.
E2001.igbt version is also available on selected rates. For more information download the brochure in download area.
110 Vdc | 5 | 10 | 15 | 20 | 30 | 40 | 50 | - | - | - | - | - | - |
220 Vdc | 5 | 10 | 15 | 20 | 30 | 40 | 50 | 60 | 80 | 100 | - | - | - |
400 Vdc | - | - | - | - | - | - | 50 | 60 | 80 | 100 | 120 | 160 | 200 |
Nominal power kW | 4 | 8 | 12 | 16 | 24 | 32 | 40 | 48 | 64 | 80 | 96 | 128 | 160 |
*other ratings available on request
Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
Power Factor | From 0,8 up to unity (depending on rectifier technology) |
Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
**available on selected ratings
DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Nominal voltage | 110/115/120/220/230/240 Vac 1-phase |
Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms | Harmonic Distortion THDv | <2% linear load; <5% non-linear load |
Dimensions | From 800 mm to 3000 mm width, 800/1000 mm depth, 2100 height | |
Cooling | Forced ventilation (optional redundant fans) | |
Colour | RAL 7035 (optional other colours) | |
Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
Front panel | Graphic display, mimic LED panel, function keys, local EPO |
Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Quality assurance, environment, health and safety: | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
Safety | IEC EN 62040-1 |
EMC | IEC EN 62040-2 |
Environmental aspects | IEC EN 62040-4 |
Test and performance | IEC EN 62040-3 VFI-SS-111 |
Protection degree | IEC 60529 |
Marking | CE (CSA/UL certified as optional) |