Borri RTB range of Industrial Thyristor Controlled 3-Phase Battery Chargers are designed and built for the harshest conditions and to provide high reliability power supply and battery charging capability. Using a powerful microprocessor to control all the functions provides reliable operations with ease of settings and communication.
Built with a rugged thyristor-controlled rectifier bridge suitable for charging nickel-cadmium or lead acid batteries while simultaneously supplying DC loads. It can also be used without batteries as a direct power supply.
RTB.igbt version is also available on selected rates. For more information download the brochure in download area.
Rating (A) | 50 | 100 | 150 | 200 | 300 | 400 | 500 | 600 | 800 | 1000 | 1600 | 2000 |
Nominal voltage | 208/380/400/415/480 Vac 3-phase ±10% |
Frequency | 50/60 Hz ±5% |
Nominal voltage | 24/48/60/110/125/220 Vdc (other voltages up to 900 Vdc on request) |
Static voltage regulation | ±1% |
Voltage ripple | ≤1-2% with and without battery depending on output voltage |
Overload capacity | < 120% for 20 min; < 150% for 2 min; > 150% for 20 s (protection electronic current limit) |
Charging characteristic |
Constant current / constant voltage (I/U as per IEC 478-1) during float charge |
Dimensions WxD (mm) | Height is 2100 mm, width and depth vary with output rated current and voltage (see the table below) | ||||||||||||
Rating | 50 | 100 | 150 | 200 | 300 | 400 | 500 | 600 | 800 | 1000 | 1600 | 2000 | |
Output voltage |
24 Vdc | 600x 800 |
600x 800 |
600x 800 |
600x 800 |
600x 800 |
800x 800 |
800x 800 |
800x 800 |
800x 800 |
1000x 800 |
2000x 800 |
2000x 800 |
48/60 Vdc |
600x 800 |
600x 800 |
600x 800 |
600x 800 |
800x 800 |
800x 800 |
800x 800 |
1000x 800 |
1000x 800 |
1000x 800 |
2000x 800 |
2000x 800 |
|
110/125 Vdc |
600x 800 |
600x 800 |
600x 800 |
600x 800 |
800x 800 |
800x 800 |
1000x 800 |
1000x 800 |
1000x 1000 |
1000x 1000 |
2000x 1000 |
2000x 1000 |
|
220 Vdc | 600x 800 |
600x 800 |
600x 800 |
800x 800 |
800x 800 |
1000x 800 |
1000x 800 |
1000x 800 |
1000x 1000 |
1000x 1000 |
2000x 1000 |
2000x 1000 |
|
Cooling | Natural convection or forced cooling depending on rating and IP protection | ||||||||||||
Colour | RAL 7035 (other colours optional) | ||||||||||||
Protection degree | IP 30 as per IEC 60529 (other protection degrees up to IP 54 optional) | ||||||||||||
Operating temperature | -10 °C to +40 °C (up to 55° C optional) | ||||||||||||
Storage temperature | -20 °C ÷ +70 °C | ||||||||||||
Altitude | < 1000 m (derating according to EN 62040-3) | ||||||||||||
Audible noise (dBA) | < 55 to 70 dBA at 1 m depending on rating and fan redundancy |
Front panel | LCD display, LED mimic, keyboard. 20 programable alarm and status LEDs |
Standard alarms | AC Fail, DC Hi, DC Low, Charger Fail, Overload, Blown Fuses, Battery Discharge, Common Alarm (many other available as standard) |
Connectivity | Potential free contacts x 8 standard, RS-485 MODBUS (optional) |
Safety | IEC EN 50178, IEC EN 62040-1 |
EMC | IEC EN 61000-6-2, IEC EN 61000-6-4,IEC EN 62040-2 |
Test and performance | IEC EN 60146 |
Marking | CE (CSA/UL certified as optional) |