Ingenio SFC

Convertitore statico di frequenza
100-2000 kVA

Borri range of Static Frequency Converters are designed and built for the harshest conditions and to provide high reliable power supply converting 50 Hz supply to 60 Hz equipment and to different voltages.

Using state-of-the-art IGBT technology with DSP (Digital Signal Processors) controls we convert the input AC power through a IGBT PFC sine-wave rectifier to DC and then to an AC sine-wave IGBT inverter to produce a full sine-wave output at the new frequency and voltage.

  • Proven advanced IGBT technology.
  • Compact design, high power density.
  • No moving elements - low maintenance.
  • High reliability and availability.
  • Precise output frequency generation.
  • Remote monitoring and control through Ethernet, Modbus TCP/IP protocols.
  • Flexible in-built features.
  • Optional operation with battery.
  • Highly customizable.
  • Easy maintenance and serviceability
  • Internal input and output switches.
  • 8 potential free contacts fault remote alarm.
  • Power and control cable markings.
  • Halogen free cable.
  • Component markings.
  • Bottom cable entry.
  • Advanced Multi-functional LCD panel.

Scheda Tecnica

Ingenio SFC: convertitore statico di frequenza 100-2000 kVA

Utility - Input

Voltage 380 – 440 V ± 10% 3P+N (or any voltage with input transformer)
Nominal supply frequency 50 or 60 Hz
Frequency tolerance ± 5 Hz
Harmonics < 3% THDi (at rated load)
Power Factor Unity

Load - Output

Capacity rating 100 kVA to 2000 kVA pf 1
Voltage 380 – 480 V (or any voltage with output transformer)
Frequency 50 or 60 Hz (consult factory for other frequencies)
Voltage harmonics < 2.5% THDv (linear load)
Overload capability 120% for 10 mins;
150% for 30 seconds
Short circuit current limit 200% for 2 seconds
Voltage accuracy 50 or 60 Hz (consult factory for other frequencies)
Frequency accuracy +/- 0.1%

Performance

Efficiency 95% Typically

General

Enclosure IP rating IP20 Cabinet (higher protection up to IP54 on request)
Operating temperature 0 - 40°C (up to 55°C with derating)
Cooling Forced air
Capacity derating with elevation -1.0 % / 100 m for application above 1000 m, 2000 m maximum
Humidity < 95% non - condensing
Noise < 65

Control interface

Digital inputs (voltage free contacts) Start; Stop/Reset
Digital outputs (relay outputs) Running (NO); Warning (NO); Fault (NC)
Relay output ratings 230 Vac 1 A

Standard

Quality assurance, environment, health and safety ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2
Environmental aspects IEC/EN 62040-4;
Test and performance IEC/EN 62040-3
Protection degree IEC 60529
Marine classifications (on request) DV, DNV, GL, ABS, CCS (++)
Marking CE