Borri AC Marine 3-Ph Uninterruptible Power System E3001 is designed and manufactured to withstand harsh environment and operating conditions of marine applications with state-of-the-art technology, providing reliable and customizable AC power backup solutions.
Borri’s E3001 is a heavy-duty on-line double conversion AC Industrial UPS with full galvanic isolation. The UPS design ensures very high reliability, safe operations and a very low mean time to repair (MTTR), achieving the highest possible availability.
The design flexibility allows it to meet almost any customer specification. E3001 UPS is a cost-effective solution delivering reliability, availability and maintainability in almost any environmental conditions.
110 Vdc | 5 | 10 | 15 | 20 | 30 | 40 | 50 | 60 | 80 | 100 | - | - | - | - | - | - | - | - |
220 Vdc | 5 | 10 | 15 | 20 | 30 | 40 | 50 | 60 | 80 | 100 | 120 | 160 | 200 | 250 | 300 | - | - | - |
400 Vdc | - | - | - | - | - | - | - | - | - | 100 | 120 | 160 | 200 | 250 | 300 | 400 | 500 | 600 |
Nominal power kW | 4 | 8 | 12 | 16 | 24 | 32 | 40 | 48 | 64 | 80 | 96 | 128 | 160 | 200 | 240 | 320 | 400 | 480 |
*other ratings available on request
Input voltage | 380/400/415 (optional 208 to 690) Vac 3-phase ±10%, 50/60 Hz ±10% |
Power Factor | From 0,8 up to unity (depending on rectifier technology) |
Input THDi | 27% 6p, 12% 12p, 5% IGBT rectifier** |
Bypass input voltage | 200/208/220 or 380/400/415 Vac 3-phase ±20% (adjustable according to inverter output voltage) |
**available on selected ratings
DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) / 400 Vdc (320÷480 Vdc range) |
Operating battery voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Nominal voltage | 200/208/220/380/400/415 Vac 3-phase |
Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms | Harmonic Distortion THDv | <2% linear load; <5% non-linear load |
Dimensions | From 800 mm to 3000 mm width, 800/1000 mm depth, 2100 height | |
Cooling | Forced ventilation (optional redundant fans) | |
Colour | RAL 7035 (optional other colours) | |
Protection degree | IP 20 as per IEC 60529 (optional up to IP 54) |
Operating temperature | -10°C to 40°C (up to 55°C with de-rating) / Storage: -20°C to 70°C |
Altitude | <1000 m (up to 2000 m de-rating according to EN 62040-3) |
Audible noise at 1 meter (dBA) | 65 to 72 (depending on rating and options) |
Front panel | Graphic display, mimic LED panel, function keys, local EPO |
Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
Safety | IEC EN 62040-1 |
EMC | IEC EN 62040-2 |
Environmental aspects | IEC EN 62040-4 |
Test and performance | IEC EN 62040-3 VFI-SS-111 |
Protection degree | IEC 60529 |
Marking | CE (CSA/UL certified as optional) |