The Borri Industrial 1 -Phase UPS E2001 Compact is designed and manufactured to withstand harsh environment and operating conditions of industrial applications with state-of-the-art technology, providing reliable and customizable AC power backup in a compact standardised solution.
Borri’s E2001 Compact is a heavy-duty on-line double conversion AC Industrial UPS with full galvanic isolation. The UPS design ensures very high reliability and safe operations; its internal constructions allows for front and easy maintenance.
The design flexibility and the wide range of configurable options allows it to meet almost any customer specification.
E2001 Compact Industrial 1-Phase UPS is a cost-effective solution delivering reliability, availability and maintainability in almost any environmental conditions.
110 Vdc | 5 | 10 | 15 | 20 | 30 |
220 Vdc | 5 | 10 | 15 | 20 | 30 |
Nominal power kW | 4 | 8 | 12 | 16 | 24 |
Input voltage | 380/400/415 Vac 3-phase ±10% (others on request), 50/60 Hz ±10% |
Power Factor | > 0,75 (depending on rectifier technology) |
Bypass input voltage | 110/115/120 or 220/230/240 Vac 1-phase ±20% (adjustable according to inverter output voltage) |
DC voltage | 110 Vdc (90÷160 Vdc range) / 220 Vdc (180÷300 Vdc range) |
Input voltage | Floating: 2.27 (VRLA), 2.2÷2.3 (VLA), 1.4÷1.5 (Ni-Cd) V/cell adjustable Boost: 2.4÷2.45 (VLA), 1.5÷1.65 (Ni-Cd) V/cell adjustable Equalizing: up to 2.35 (VRLA), up to 2.7 (VLA), up to 1.7 (Ni-Cd) V/cell adjustable |
Battery technologies | Maintenance free Lead Acid and Ni-Cd / Vented Lead Acid and Ni-Cd, Li-Ion battery compatible |
Nominal voltage | 110/115/120 or 220/230/240 Vac 1-phase |
Frequency | 50/60 Hz (selectable), ±0.001 Hz free running, ±2 Hz synchronized with mains |
Voltage regulation | ±1% static; ±5% dynamic (80% load change), <40 ms recovery time |
Overload capacity | 125% for 10 min; 150% for 1 min; 200% for 100 ms | Harmonic Distortion THDv | <2% linear load; <5% non-linear load |
Dimensions WxD (mm) | 600x640x1900 | 800x800x2100 |
Cooling | Forced ventilation (optional redundant fans) | |
Colour | RAL 7035 (optional other colours) | |
Protection degree | IP 20 as per IEC 60529 (optional up to IP 42) |
Operating temperature | -10° C to 40° C (up to 55° C with de-rating) / Storage: -20° C to 70° C | |
Altitude | < 1000 m (up to 2000 m de-rating according to EN 62040-3) | |
Audible noise at 1 meter (dBA) | <65 |
Front panel | Graphic display, mimic LED panel, function keys, local EPO |
Connectivity | Included: USB, alarm relay card, terminal block for auxiliary contacts |
Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
Safety | IEC EN 62040-1 |
EMC | IEC EN 62040-2 |
Environmental aspects | IEC EN 62040-4 |
Test and performance | IEC EN 62040-3 VFI-SS-111 |
Marking | CE (CSA/UL certified as optional) |