The industrial modular UPS UMB AC07 is designed and developed to withstand harsh industrial environment and operating conditions of industrial applications with state-of-the-art technology, providing reliable and customized system solutions.
The modular design ensures a very high reliability and a very low mean time to repair (MTTR) making the Borri UMB AC07 UPS system with the highest possible availability.
Borri industrial modular UPS provides scalability and very high operating efficiency, even at partial loads, the real running costs are minimized without the need to compromise on power quality. Each UMB AC07 modular UPS module is a highly efficient double conversion, serial on-line UPS (VFI-SS-111).
Rating (kW) | 20 | 40 | 60 | 80 | 100 | 120 |
Module nominal power (kW) | 20 (3x6.7 kW) |
Input voltage | 380/400/415 Vac 3-phase with neutral |
Input frequency | 45/65 Hz (auto-sensing or selectable by the User) |
Input voltage range | 400 V +15%/-20% |
Power factor | 0.99 |
Input THDi | <3% |
Bypass input voltage | 380/400/415 Vac 3-phase ±20% |
Nominal voltage | 216 V to 252 V | |||||
Battery technologies | Maintenance-free Lead Acid (VRLA-AGM) | |||||
Charging current (A) | 7.5 | 15 | 22.5 | 30 | 37.5 | 45 |
Nominal voltage | 380/400/415 Vac 3-phase + N +/- 1%; 220/230/240 Vac 1-phase +/- 1% (only 20 kW) |
Frequency | 50/60 Hz |
Voltage regulation | ±1% static; dynamic: IEC/EN 62040-3 Class 1 |
Overload capacity | 115% for 10 min; 135% for 60 sec |
Harmonic Distortion THDv | <1% linear load; <5% non-linear load |
Dimensions WxDxH (mm) | 600x800x2100 | 1200x800x2100 | ||||
Cooling | Forced ventilation | |||||
Colour | RAL 7035 (others on option) | |||||
Protection degree (IEC 60529) | IP 20 (optional up to IP 42) | |||||
Efficiency (AC/AC) | Up to 96% |
Operating temperature | 0°C to +40°C (derated up to 55°C)/ Storage: 10°C to +70°C |
Altitude | < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m |
Audible noise at 1 meter (dBA) | 50 to 65 (depending on power rating) |
Front panel | Cabinet graphic display, mimic LED panel and keyboard, local EPO |
Connectivity | Included: RS232 card, USB. Optional: Modbus-RTU, PROFIBUS DP, MODBUS TCIP |
Quality assurance, environment, health and safety | ISO 9001:2008, ISO 14001:2004, BS OHSAS 18001:2007 |
Safety | IEC EN 62040-1 |
EMC | IEC EN 62040-2 |
Environmental aspects | IEC EN 62040-4 |
Test and performance | IEC EN 62040-3 VFI-SS-111 |
Protection degree | IEC 60529 |
Marking | CE |