INGENIO COMPACT

3-phase UPS 10-20 kVA

Ingenio Compact three-phase UPS provides a perfect solution for critical power applications such as networks and servers, small and medium data centers, telecommunication. Ingenio Compact is a three-phase UPS available in the 10-20 kVA range with on-line double conversion technology and parallel redundant configuration.

  • Input power factor correction 0.99 for clean mains
  • Unity output power factor for more power
  • Easy to use touch screen display
  • Easy to parallel
  • Low running cost: high efficiency and ECO mode reduce overall power losses and thus energy costs.
  • Reduced commissioning and floor space related costs and lower environmental footprint with transformer free design and common battery management.
  • Fast installation and monitoring: innovative and user-friendly design with built-in LCD touch screen.
  • Easy maintenance thanks to a removable tray design, achieving optimal sizing of battery capacity and minimal investment.
  • On-line double conversion and ECO modes for total protection, low running costs and environmental impact.
  • Full rated power, ensuring optimal UPS sizing and utilization.
  • Transformer free design for light small size layout.
  • Full IGBT technology and electronic PFC, ensuring 0.99 input PF and low THDi for maximum upstream sources compatibility.
  • Wide input voltage range to save battery life.
  • Wide range of configurations with internal and external batteries for low TCO compact solutions.
  • Parallel-redundant up to six units, to increase system redundancy.
  • Innovative design allows for fast installation.
  • Removable tray design for easy battery maintenance.
  • Comprehensive set of communication options for total remote monitoring of equipment operation.
  • Fully compliant with all international product standards for maximum quality guarantee.

Tech Specs

INGENIO COMPACT: 3-phase UPS 10-20 kVA

Rating (kVA) 10 15 20
Nominal power (kW) 10 15 20
UPS dimensions WxDxH (mm) 440x800x800
UPS weight (kg) 75 76 76
UPS weight with internal battery (kg) 150 165 165
External battery module
dimensions WxDxH (mm)
550x650x1200
Battery configuration Internal (standard): 180 cells; external: 156/240 cells Internal (standard): 216 cells; external: 192/240 cells

Input

Connection type Hardwired 4w
Nominal voltage 400 Vac 3-phase with neutral
Voltage tolerance -20%, +15% (rectifier); ±10% (bypass)
Frequency and range 50/60 Hz, 45 to 70 Hz
Power factor 0.99
Current distortion (THDi) <3%

Output

Connection type Hardwired 4w
Nominal voltage 380/400/415 Vac 3-phase with neutral
Frequency 50/60 Hz
Power factor Up to 1, without power derating
Overload capacity 110% for 60 min, 125% for 10 min, 150% for 1 min
Efficiency (AC/AC)* Up to 98%
Classification by IEC/EN 62040-3 VFI-SS-11

*according to IEC/EN 62040-3

Connectivity and function extensions

Front panel Touch screen display
Remote communication Included: serial RS232; backfeed protection monitoring contact, remote EPO contact.
Optional: 2 slots for SNMP adapter, ModBus-RTU, contact relay card
Optional function extensions Isolation transformer; transformers/autotransformers for voltage adjustment;
external maintenance bypass; custom battery cabinets; wall-mounted battery fuse
switch box; battery thermal probe; parallel kit; other options on request

System

Protection degree IP 20
Colour RAL 9005
Installation layout 30 cm wall-gap
Accessibility Positioning casters; bottom cable entry

Environmental

UPS operating temperature range 0°C to +40°C
UPS storage temperature range -10°C to +70°C
Altitude (AMSL) < 1000 m without power reduction, > 1000 m with reduction of 0.5% per 100 m
Audible noise at 1 m (dBA) <52

Standards and certifications

Quality assurance,
environment, health and safety
ISO 9001, ISO 14001, ISO 45001
Safety IEC/EN 62040-1
EMC IEC/EN 62040-2
Environmental aspects IEC/EN 62040-4
Test and performance IEC/EN 62040-3
Protection degree IEC 60529
Marking CE
TOP